Installation Instructions
4.0 Connections
Profile
• Unit water connection a ½” BSP female flexible connection. Use the
flexible connector supplied for the connection between the isolating cock
and the solenoid / float valve.
NOTE: In areas where water pipes freeze, a low level drain tap or
pressure expansion control valve provision will be needed to drain
the water piping to prevent damage to the air conditioner. The
customer should also be advised on its operation by the dealer /
installer.
• Ensure the approved water supply pipe is of the correct length and is
secured to prevent tension on the solenoid / float valve fittings.
• The supply pipe should be 12mm copper pipe or similar approved. A ¼
turn ball isolating valve must be installed on the supply pipe near the unit
for ease of maintenance. Do not use duo or non-return valves of any kind
including stop taps with jumper washer.
NOTE: Non return type valves can have an effect on the operation of
the water solenoid valves. Lock up and damage can be caused. Non
return valves are not required as the product conforms to MP52 Spec
101:2001 Plumbing safety licence.
• Before connecting the supply pipe flush
it of any swarf or debris that may cause
the float valve or solenoid to leak.
NOTE: Failure of the Solenoid valve
or Ball Float due to debris or swarf
will not be covered by warranty and
is therefore the responsibility of the
installer / owner.
4.3. Water Drain Connections
4.3.1. Fitting The Overflow Assembly
The overflow fitting connection size is 50mm BSP.
STEP 1. Remove nut and rubber washer from
over flow assembly.
STEP 2. Place rubber washer inside the tank and
fit overflow assembly.
STEP 3. Fit the nut to the overflow fitting on the
underside of the tank and tighten
ensuring no leaks.
Page 13